      PORTABLE GIS PARTIAL DISCHARGE DIAGNOSTIC EQUIPMENT(APDMS)

      System Overview

      The Advanced Partial Discharge Monitoring System (APDMS) is a device that can efficiently diagnose abnormalities in power facilities in live conditions where partial discharge diagnostic devices and sensors for partial discharge detection are not installed.
      APDMS acquires a partial discharge signal at 100M/s and includes the ability to remove noise by comparing noise and PD signals, which is an innovative device that can increase the reliability of fault diagnosis.

      APDMS TECHNICAL SPECIFICATIONS

      Frequency Band 100 ~ 1,500 [MHz]
      Signal Detection Area 0[dBm] ~ -65[dBm]
      Impedance 50 [¥Ø]
      Number of Input Ports 16 Channel (Noise Channel 4ch, 8ch)
      Connector Type N-Type
      Number of Signal Samples 100M/Second
      Communication Ethernet 10/100 base-t(Used UI Communication)
      Input Power 220VAC / 60Hz (110VAC / 50Hz)
      Device Size 540x420x220(mm)
      Device Weight About 15kg

      HMI

      It provides a familiar operating program (HMI) and can be diagnosed with a total of five types of partial discharge and noise signals, including inductive discharge, floating electrode discharge, corona discharge, and insulation abnormal discharge.
      Also, the partial discharge signal is displayed by PRPD (Phase Resistance) and PRPS (Phase Resistance).
      APDMS may store diagnostic results by diagnostic programs, and output this results.

      HMI TECHNICAL SPECIFICATIONS
      CPU Intel Core i7 or higher
      GRAPHIC GeForce GTX1050 or higher
      OS MS¡¡Windows 10 or higher
      Diagnostic Algorithm Neural Network Algorithm
      Signal Type Ethernet 10/100 base-t Used UI Communication
      RS-232 38,400bps Used Debug
      View PRPS, PRPD

      SENSOR

      The sensor on the APDMS consists of a sensor available for GIS and a Noise Sensor.

      • The GIS sensor is used for obtaining partial discharge signal to obtain partial discharge signal.
      • Noise Sensor is installed for measuring the discharge signal generated in narrow space, or noise gauge that occurs in narrow space.
      • UHF SPACER SENSOR

      • UHF NOISE SENSOR

      SENSOR TECHNICAL SPECIFICATIONS
      Impedance 50 [¥Ø]
      Connector Type N-Type
      Signal Band GIS Sensor 100 ~ 1500 [MHz]
      Noise Sensor 100 ~ 3000[MHz]